Core Advantages & Features
-
Hermetically Sealed DesignAll high-voltage components are enclosed within a stainless steel gas compartment, ensuring insulation integrity and maintenance-free operation.
01 -
Compact ConstructionIdeal for confined spaces such as wind turbine towers or container substations.
02 -
Advanced Welding Technology3mm 304 stainless steel tank welded with TRUMPF five-axis laser system delivers exceptional airtightness and aesthetics.
03 -
Helium Leak Detection AssuranceSEILER automated testing guarantees a leakage rate below 0.01% per year and a service life exceeding 30 years.
04 -
Modular ConfigurationFlexible module arrangement supports diverse distribution schemes and system expansion.
05 -
Fully Insulated BusbarsExtended busbars are insulated and shielded to enhance reliability and safety.
06 -
Misoperation PreventionMechanical interlocking system provides simple and effective safety assurance.
07 -
Durable MechanismsLoad switch lifespan reaches 5,000 operations; vacuum circuit breaker up to 10,000 operations.
08 -
High Transfer CapabilityLoad switch-fuse combination supports transfer current of 840A.
09 -
Intelligent Automation OptionsFactory-automated solutions enable intelligent switching and consistent product quality.
10 -
Automated ConsistencyA fully automated assembly line ensures product consistency.
11 -
Strong Arc ExtinguishingThe use of a gas-type load switch provides strong arc extinguishing capability.
12
Technical Parameters
| Basic Parameters | |
|---|---|
| Rated voltage | 40.5 kV |
| Rated frequency | 50 Hz / 60 Hz |
| Rated current | C Unit: 630 A, F Unit: 63 A, V Unit: 630 A |
| Ratedp power frequency withstand voltage | 95 kV / 118 kV (isolation fracture) |
| Rated lightning impulse withstand voltage | 185 kV / 215 kV (isolation fracture) |
| Mechanical life | C Unit: 5000 times, F Unit: 5000 times, V Unit: 10000 times |
Rated short-circuit breaking current | F Unit: 31.5 kA, V Unit: 20 kA / 25 kA |
| Rated making current | C Unit: 50 kA, F Unit: 80 kA, V Unit: 50 kA / 63 kA |
| Rated transfer current | F Unit: 1400 A |
| Rated short-time withstand current of main circuit (4s) | C Unit, V Unit: 20 kA (4s), 25 kA (3s) |
| Rated peak withstand current of main circuit | C Unit, V Unit: 50 kA / 63 kA |
| Internal arc classification | AFLR, 25kA, 1s |
| Rated operating pressure (gauge pressure at 20℃) | 0.04 MPa |
| Minimum operating pressure (gauge pressure at 20℃) | 0.03 MPa |
| Enclosure protection class | IP41 |
| Gas tank protection class | IP67 |
| Annual gas leakage rate | ≤0.01% |
Product Documents
-
Product Brochure
-
DQS-40.5 SF6 Fully Insulated Ring Main Unit
2025-11-25
Download PDF
The company consistently maintains robust innovative vitality, standing at the forefront of the industry and driving its advancement. Through cutting-edge technologies and products, it achieves goals of energy conservation, environmental protection, quality enhancement, and consumption reduction, continuously contributing to the development of a resource-efficient and environmentally friendly society.